Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range 0 - 75 mbar
APPLICATIONS
DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms
WARNING
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference.
This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device.
SPECIFICATIONS
Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error
Thermal Effects Temperature compensated across the full spectrum of capability
Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC
Zero Point Calibration Automatic with function or Manual push-button Auto-Zero
Response Time 4.0 0.8 sec, Selectable via Jumper
Technical Specifications Media Compatibility Dry air or non-aggressive gases
Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive
Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing
Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3
Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm)
Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2
Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)
Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure
Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k
Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4
The DPT30-R8 offers highly accurate differential pressure measurement, covering a range from 0 to 75 mbar with only 1% full-scale deviation. The device can be fitted in various industrial applications, including monitoring air flow, clean room pressures, and building automation systems. Its versatile outputs (4-20mA and 0-10V) allow easy integration into different control setups.
With a compact design and wall/panel mounting options, the DPT30-R8 can be easily installed in tight spaces. The screw terminal block ensures secure electrical connections, and calibration is streamlined with push-button zero and span adjustment. The device is supplied with mounting screws and a detailed instruction manual for hassle-free setup.
Built with a polycarbonate enclosure and rated IP65, the transmitter offers solid protection against dust and moisture. It operates reliably from -10C to +60C, making it suitable for demanding environments. The temperature-compensated signal processing and robust materials ensure stability and longevity, even in fluctuating industrial conditions.
FAQ's of Sensocon USA Differential Pressure Transmitter Series DPT30-R8 - Range 0 - 75 mbar:
Q: How do I calibrate the DPT30-R8 differential pressure transmitter?
A: Calibration of the DPT30-R8 is straightforward using the built-in push button adjustment for both zero and span. Detailed steps are provided in the instruction manual, enabling in-field calibration without specialized equipment.
Q: What are the main applications for this transmitter?
A: The DPT30-R8 is primarily used in HVAC systems, air flow measurement, clean room monitoring, filter status checks, and building automation. Its capability to measure the differential pressure of steam, oil, and gas also makes it valuable for a wide range of industrial processes.
Q: When should I use this transmitter instead of a standard pressure sensor?
A: Use the DPT30-R8 when you need to measure low differential pressures with high accuracy, particularly for monitoring pressure differences rather than absolute pressure. It is especially suitable for monitoring clean environments and air handling units.
Q: Where can the DPT30-R8 be installed?
A: Thanks to its IP65-rated polycarbonate enclosure and compact dimensions, the DPT30-R8 can be wall- or panel-mounted in both indoor and outdoor settings, provided environmental conditions are within its specified operating range of -10C to +60C.
Q: What type of output signals does the transmitter provide?
A: This transmitter offers both 4-20mA (2-wire) and 0-10V (3-wire) output signals, ensuring seamless compatibility with a broad spectrum of control systems and data acquisition equipment.
Q: How does the transmitter ensure reliable measurements in varying temperatures?
A: The DPT30-R8 uses temperature-compensated signal processing technology, maintaining measurement precision even when ambient temperatures fluctuate between -10C and +60C.
Q: What benefits does the integrated LCD display offer?
A: The digital LCD display provides clear, real-time visualization of pressure readings, simplifying monitoring and on-site diagnostics without the need for external meters.