About Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 1.25 mbar
Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 1.25 mbar
APPLICATIONS
DPT-R8 series devices are commonly used in HVAC/R systems for: Fan, blower and filter monitoring Pressure and flow monitoring Valve and damper control Pressure monitoring in clean rooms
WARNING
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
Failure to observe safety information and comply with instructions could result in PERSONAL INJURY, DEATH AND/ OR PROPERTY DAMAGE.
To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
Retain these instructions for future reference.
This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by Sensocon. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced, knowledgeable, technicians to install this device.
SPECIFICATIONS
Performance Accuracy (at applied pressure) Ranges < 0.5 inWC = 0.01 inWC Ranges 0.5 inWC = 1.5% inWC Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error
Thermal Effects Temperature compensated across the full spectrum of capability
Overpressure Proof Pressure: 100 inWC Burst Pressure: 120 inWC
Zero Point Calibration Automatic with function or Manual push-button Auto-Zero
Response Time 4.0 0.8 sec, Selectable via Jumper
Technical Specifications Media Compatibility Dry air or non-aggressive gases
Measuring Units (select via Jumper) Pa, kPa, mbar, inWC, mmWC Measuring Element Piezoresistive
Environment: Operating Temperature: 14 122F (-10 50C) Storage Temperature: -4 158F (-20 70C) Humidity: 0 to 95 % rH, non condensing
Physical Case Dimensions: 3.54 x 3.74 x 1.4 (90.0 x 95.0 x 36.0 mm) Weight: 5.3 oz (150 g) Mounting: 2 each 0.1875 (4.3 mm) screw holes, one slotted Materials: Case: ABS (UL 94 V-0 Approved) Lid: PC (UL 94 V-1 Approved) Protection standard: IP54 / NEMA3
Display (optional) 3 1/2 Digit LCD Backlit Display 2-Line Display (12 character/line) Size: 1.81 W x 0.57 H (46.0 x 14.5 mm)
Electrical connections: 4 screw terminal block Wire: 12-24AWG (0.2 1.5 mm2
Cable Entry Strain Relief: M16 Knockout : 0.625 (16mm)
Pressure Fittings 3/16 (5.2mm) barbed brass + High pressure Low pressure
Electrical Voltage Circuit: 3-wire ([V Out], 24V, GND) Input: 24VAC or VDC, 10% Output: 0-10V or 0-5V, selectable via Jumper Power Consumption: <1.0W Resistance Minimum: 1k
Current Circuit: 3-wire (mA Out, 24V, GND) Input: 24VAC or VDC, 10% Output: 4
Highly Accurate and Rapid Pressure MeasurementThe DPT10-R8 delivers an outstanding measurement accuracy of 1% of span, with a rapid response time under one second. Its factory-calibrated, capacitive differential pressure sensor makes it suitable for critical and dynamic environments, such as process control and industrial automation, where precise pressure monitoring is essential.
User-Friendly Installation and OperationWith a compact ABS plastic housing and smooth finish, the DPT10-R8 ensures easy wall or panel mounting. The 6 mm barbed ports allow straightforward pressure hose connections, and manual zero adjustment is possible via a push button. Its screw terminal electrical connection further simplifies setup, reducing installation time and complexity.
Versatile and Robust for Industrial UseBuilt for industrial settings, this transmitter is suitable for a variety of media including steam, oil, and gas. Its IP54-rated enclosure protects against dust and moisture, while silicone seals enhance durability. The DPT10-R8 is compliant with CE and RoHS standards, underscoring its reliability, safety, and commitment to environmental guidelines.
FAQ's of Sensocon USA Differential Pressure Transmitter Series DPT10-R8 - Range 0 - 1.25 mbar:
Q: How do I install the DPT10-R8 differential pressure transmitter?
A: The DPT10-R8 transmitter can be mounted on a panel or wall using the provided mounting screws. Connect the pressure lines to the 6 mm barbed ports, and wire the device using the screw terminal block according to the instruction manual. Ensure the transmitter is supplied with 10-30 VDC power.
Q: What types of media can this transmitter measure pressure for?
A: This model is suitable for measuring the differential pressure of steam, oil, and gas. Its industrial-grade capacitive sensor ensures reliable operation across these media types in demanding environments.
Q: When should I use the manual zero adjustment?
A: Manual zero adjustment is recommended after installation or whenever the device displays a shift from the baseline zero point. The onboard push button allows you to reset the sensor zero easily, ensuring measurement accuracy.
Q: Where can I use the DPT10-R8 in my facility?
A: The DPT10-R8 is designed for use in indoor industrial environments where monitoring of low differential pressures is required, such as HVAC systems, cleanroom monitoring, or process automation lines.
Q: What process does the transmitter use to provide output signals?
A: It employs a capacitive differential pressure sensor to sense pressure differences and converts this to a standardized 4-20 mA current output (2-wire loop powered), which is widely compatible with industrial PLCs and control systems.
Q: What are the benefits of the DPT10-R8's IP54 rating and ABS plastic housing?
A: The IP54 rating protects the device from dust ingress and splashing water, while the durable ABS plastic housing ensures long-lasting performance in industrial settings. These features reduce downtimes and maintenance demands.