Back to top
Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa
Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa Specification

  • Grade
  • Industrial
  • Outer Size
  • Enclosure Size Approx. 4-1/2 Diameter
  • Thread
  • 1/8 NPT Female
  • Seal Material
  • Silicone
  • Display
  • Analog (with Setpoint Switches)
  • Sensor Type
  • Photohelic Differential Pressure Sensor
  • Material
  • Polycarbonate Housing with Aluminum Internals
  • Dial Material
  • Aluminum with Printed Scale
  • Pointer Material
  • Anodized Aluminum
  • Processing Type
  • Electromechanical Integration
  • Diameter
  • 114 mm (4.5 inches)
  • Glass Size
  • Standard Clear (Dome Lens)
  • Mount Type
  • Surface and Flush Mount
  • Scale Range
  • 0 to 1 kPa
  • Accuracy
  • 2% of Full Scale
  • Finishing
  • Black Polycarbonate Housing
  • Measure Pressure Of
  • Air and Compatible Gases
  • Accessories
  • Instruction manual, mounting hardware
 

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa Trade Information

  • Payment Terms
  • Cash on Delivery (COD), Cash Advance (CA), Cash Against Delivery (CAD), Cash in Advance (CID)
  • Main Export Market(s)
  • Asia
  • Main Domestic Market
  • Himachal Pradesh, Andaman and Nicobar Islands, Pondicherry, South India, North India, East India, Assam, Arunachal Pradesh, Bihar, Chandigarh, Goa, Chhattisgarh, Jammu and Kashmir, Jharkhand, Karnataka, Mizoram, Meghalaya, Manipur, Punjab, Rajasthan, Sikkim, Tamil Nadu, Telangana, Tripura, West Bengal, Kerala, Nagaland, Uttarakhand, Daman and Diu, Dadra and Nagar Haveli, Lakshadweep, Maharashtra, Haryana, Delhi, Gujarat, Uttar Pradesh, Madhya Pradesh, Andhra Pradesh, Central India, Odisha, West India, All India
 

About Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa

Series 3000MR/3000MRS Photohelic® Switch/Gage

Combines Differential Pressure Gage with Low/High Set-Points,Compact Size

 

 ModelDescription 
 3000MRS-1 kPaPressure Switch/Gage,Range 0-1 kPa, .02 minor divisions.
 

 

Includes

  • mounting ring, snap ring
  • 18" cable assembly
  • (2) 3/16" tubing to 1/8" NPT adapters
  • (2) 1/8" NPT pipe plugs
  • (4) 6-32 x 1-1/4" RH machine screws (panel mounting)
  • (3) 6-32 x 5/16" RH machine screws (surface mounting)

he Series 3000MR Photohelic® Switch/Gage combine the functions of a precise, highly repeatable differential pressure switch with a large easy-to-read analog pressure gage employing the durable, time-proven Magnehelic® gage design. Switch setting is easy to adjust with large external knobs on the gage face. Gage reading is unaffected by switch operation - will indicate accurately even if power is interrupted. Solid state design now results in greatly reduced size and weight. Units can be flush mounted in 4-13/16" hole or surface mounted with hardware supplied. 3000MR models employ versatile electromechanical relays with gold over silver contacts - ideal for dry circuits.

Gage accuracy is ±2% of full scale and switch repeatability is ±1%. Switch deadband is one pointer width - less than 1% of full scale. Compatible with air and other non-combustible, non-corrosive gases, they can be used in systems with pressures to 25 psig.

Applications

  • Fan Control
  • Damper Control
  • Environmental Pollution Control

Approvals

  • CE Approval
  • GOST-R Certificate

Specification

Service Air and non-combustible, compatible gases 
Accuracy ±2% of FS at 70°F 
Pressure Limits -20" Hg to 25 psig 
Temperature Limits 20 to 120°F 
Process Connections 1/8 female NPT (duplicated side and back) 
Size 4" dial face, 5" O.D. x 3-1/8" 
 Weight1.8 lb 
 Switch Specifications 
 Switch TypeEach setpoint has 1 Form C relay (SPDT) 
 Relay Contacts(resistive load) 1 Form C rated 1.0A @ 30 VDC, 0.3A @ 110 VDC or 0.5A @ 125 VAC. Gold over clad silver - suitable for dry circuits 
 Electrical Connections18" cable assembly with 8 conductors 
 Power Requirements24 VDC, regulated ±10% 
 Mounting OrientationDiaphragm in vertical position 
Set Point Adjustment Adjustable knobs on face 
 Agency ApprovalsCE 

   



Precise Differential Pressure Monitoring

The Dwyer 3000MRS delivers accurate differential pressure readings with a 2% full-scale accuracy and 1% repeatability. Its analog display provides clear visibility, while instant mechanical response ensures that pressure changes are detected and processed immediately, helping maintain optimal environmental conditions in your facility.


Rugged, Versatile Design for Industrial Use

Created for demanding industrial settings, this photohelic switch/gauge features a tough polycarbonate body with aluminum internals. The IP54 front enclosure safeguards against dust and water splashes, and flexible mounting optionssurface or flushaccommodate a variety of installation preferences, making it suitable for diverse pressure monitoring applications.


Reliable Electromechanical Integration

Combining analog indication with dual SPDT relay setpoints, the 3000MRS makes process control straightforward. Its electromechanical integration streamlines setup and usage, while external zero adjustment enhances on-site calibration. The gauge measures pressures in air and compatible gases, supporting critical control applications such as filter monitoring, fan control, and clean room management.

FAQs of Dwyer 3000MRS Photohelic Switch/Gauge 0 to 1 kPa:


Q: How does the Dwyer 3000MRS Photohelic Switch/Gauge operate?

A: The Dwyer 3000MRS operates by sensing differential pressure between its high and low 1/8" NPT ports, displaying the value on an analog gauge, and activating two independently adjustable SPDT relay switches if setpoints are exceeded. This dual functionality enables both visual monitoring and automatic process control.

Q: What applications are suitable for the 3000MRS model?

A: This gauge is ideally suited for filter monitoring, clean room pressure management, fan control, and general process control in industrial environments, where quick response and reliable switching are essential for maintaining system performance and safety.

Q: Where should the Photohelic 3000MRS be installed for accurate readings?

A: Install the gauge at a location representative of the true differential pressure you wish to monitor, connecting the high and low ports to the appropriate areas. It can be surface-mounted or flush-mounted in a panel, and is designed to be used in environments within its specified operating temperature (20 to 140F / -6 to 60C).

Q: What is the process for making electrical connections to this gauge?

A: Electrical connections are made to screw terminals on the unit. Power can be supplied at either 24 VAC or 120/240 VAC (depending on the model), and the SPDT relay outputs can be wired to external control devices or alarms. Ensure power is disconnected during installation for safety.

Q: How is zero adjustment handled on this device?

A: External zero adjustment allows you to calibrate the gauge while it remains installed, ensuring accurate and reliable readings in your specific application. Simply follow the procedure in the instruction manual using the adjustment control provided.

Q: What are the benefits of using the Dwyer 3000MRS over other pressure gauges?

A: The 3000MRS combines precise analog measurement, instantaneous response, and dual set-point control, all in a robust industrial housing. Its versatility, reliable performance, and easy integration into control systems make it an excellent choice for critical air and gas pressure monitoring tasks.

Q: When should you consider maintenance or recalibration of the 3000MRS?

A: Regular maintenance and periodic recalibration should be considered according to your facilitys requirements or whenever readings appear inconsistent. Cleaning the external lens, checking for leaks at the ports, and confirming zero adjustment help maintain optimal performance over time.

Tell us about your requirement
product

Price:

Quantity
Select Unit

  • 50
  • 100
  • 200
  • 250
  • 500
  • 1000+
Additional detail
Mobile number

Email

More Products in Series 3000MR/3000MRS | Photohelic Switch Category

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 125 Pa

Dwyer 3000MRS Photohelic Switch/Gauge 0 to 125 Pa

Measure Pressure Of : Other, Air and compatible gases

Finishing : Other, Textured finish housing

Dwyer A3000-100CM Photohelic Pressure Switch Gauge Range

Dwyer A3000-100CM Photohelic Pressure Switch Gauge Range

Measure Pressure Of : Oil, Gas

Finishing : Matte, Polished