About Sensocon USA 212-D015P-3 Differential Pressure Transmitter
Sensocon USA 212-D015P-3 Differential Pressure Transmitter
- Maximum Pressure: Ranges 5 PSI (35 kPa) = 15 PSI (100kPa) MaxRanges > 5 PSI (35 kPa) = 30 PSI (200kPa) Max
- Media compatibility: Air and compatible non-combustible, non-corrosive gases
- Accuracy: Ranges 4" w.c. (1kPa) 1.0%Ranges 5" w.c. (1.25kPa) 0.25%
- Temperature Ranges: Compensated: 15 to 120F (-10 to 50C)Operating: -10 to 155F (-25 to 70C)
- Thermal Effect: +/- 0.028% FS/F (+/- 0.50% FS/C)
- Stability: +/- 0.25% FS/year
- Output Signal: 4-20 mA, 2-wire or 0 - 10 V
- Loop Resistance: 250 @ 24 VDC
- Power Supply: 12-30 VDC
- Enclosure Rating: IP 65
- Electrical Connections: screw terminals
- Electrical Entry: PG7 Cable Gland
- Process Connection: Barbed fittings for 3/16 flexible tubing
- Agency Approvals: CE
Reliable Industrial Pressure MeasurementThe Sensocon USA 212-D015P-3 is engineered to deliver precise differential pressure readings for critical HVAC, cleanroom, and industrial automation applications. Its fast response and robust construction ensure stable performance, while the digital LCD enhances clarity for real-time monitoring.
Seamless Installation & OperationDesigned for surface or panel mounting, this transmitter includes both hardware and easy-to-follow instructions. Screw terminal electrical connections support swift wiring, while the IP54 enclosure ensures protection against dust and incidental moisture, making it suitable for challenging environments.
FAQs of Sensocon USA 212-D015P-3 Differential Pressure Transmitter:
Q: How do I install the Sensocon 212-D015P-3 differential pressure transmitter?
A: Installation involves securely mounting the unit to a surface or panel using the provided screws, then connecting wiring to the screw terminal block. The device should be connected to a 9-30 VDC power supply and linked to the equipment monitoring the 4-20 mA output.
Q: What type of media is compatible with this pressure transmitter?
A: The transmitter is designed to measure dry air or non-corrosive gases only. It is not suitable for use with corrosive substances or liquids.
Q: When should I use this sensor in my application?
A: This transmitter is ideal when precise, rapid differential pressure monitoring is needed, such as in HVAC systems, cleanrooms, or process automation involving compatible gases within a 015 PSI range.
Q: Where can this transmitter be installed for optimal performance?
A: Install the device in environments where the temperature remains between 0 and 60C (32 to 140F) and away from areas exposed to direct water or corrosive gases, utilizing its IP54 rating for limited dust and moisture protection.
Q: What process does the transmitter use to display and transmit data?
A: It electronically senses differential pressure and displays the value on the digital LCD. Simultaneously, it outputs a corresponding current (4-20 mA) signal for integration with control systems.
Q: How does using this transmitter benefit industrial operations?
A: It delivers fast, accurate differential pressure monitoring, supports automated control through reliable signaling, and is durable enough for demanding environments, reducing maintenance and improving operational efficiency.