About Sensocon USA 212-D010P-3 Differential Pressure Transmitter
Sensocon USA 212-D010P-3 Differential Pressure Transmitter
- Maximum Pressure: Ranges 5 PSI (35 kPa) = 15 PSI (100kPa) MaxRanges > 5 PSI (35 kPa) = 30 PSI (200kPa) Max
- Media compatibility: Air and compatible non-combustible, non-corrosive gases
- Accuracy: Ranges 4" w.c. (1kPa) 1.0%Ranges 5" w.c. (1.25kPa) 0.25%
- Temperature Ranges: Compensated: 15 to 120F (-10 to 50C)Operating: -10 to 155F (-25 to 70C)
- Thermal Effect: +/- 0.028% FS/F (+/- 0.50% FS/C)
- Stability: +/- 0.25% FS/year
- Output Signal: 4-20 mA, 2-wire or 0 - 10 V
- Loop Resistance: 250 @ 24 VDC
- Power Supply: 12-30 VDC
- Enclosure Rating: IP 65
- Electrical Connections: screw terminals
- Electrical Entry: PG7 Cable Gland
- Process Connection: Barbed fittings for 3/16 flexible tubing
- Agency Approvals CE
Precise Digital Measurement for Demanding EnvironmentsThe Sensocon 212-D010P-3 provides precise differential pressure readings in a variety of settings, from HVAC systems to cleanrooms. Its accuracy (1.0% of full scale) and rapid response time (<5 ms) enable efficient monitoring and control. The clear digital LCD simplifies at-a-glance readings and adjustments, while the robust design ensures longevity and stability in industrial environments.
Flexible and Durable for Easy IntegrationEngineered for convenient integration, this transmitter features dual 1/8 NPT female connections and supports both wall and panel mount configurations. The included mounting kit makes installation straightforward, while powder-coated ABS housing provides protection against harsh conditions in indoor or sheltered industrial locations. The IP65 rating furthers its reliability in dusty or moist environments.
FAQs of Sensocon USA 212-D010P-3 Differential Pressure Transmitter:
Q: How do you install the Sensocon 212-D010P-3 Differential Pressure Transmitter?
A: The transmitter can be mounted on a panel or wall using the provided mounting kit. Simply connect the 2 x 1/8 NPT female pressure fittings to your ducts or pipes, secure the unit with screws, and follow the steps outlined in the included instruction manual for wiring and initial setup.
Q: What is the benefit of the digital LCD display on this pressure transmitter?
A: The integrated digital LCD display provides precise, real-time readings, making pressure monitoring more accessible and minimizing manual interpretation errors during routine checks or troubleshooting.
Q: When should you consider adjusting the zero and span settings?
A: Adjust the zero and span whenever you perform installation, undergo regular maintenance, or observe any drift in readings. The digital push-button adjustment feature streamlines this process, ensuring lasting accuracy over time.
Q: Where can this transmitter be used effectively?
A: This model is ideal for use in industrial and commercial HVAC systems, filter monitoring, cleanroom pressure control, and building automation projects, especially where accurate monitoring of air or non-corrosive gas pressure is essential.
Q: What is the accuracy of this transmitter and what gases can it measure?
A: The Sensocon 212-D010P-3 provides an accuracy of 1.0% of full scale and is engineered specifically for the measurement of air and non-corrosive gases.
Q: How does the IP65 protection class benefit the transmitter?
A: IP65-rated protection ensures the unit is resistant to dust ingress and low-pressure water jets, which is valuable in challenging industrial environments where such exposures are common.