About Dwyer EDPS-04-1-N Adjustable Differential Pressure Switch
Dwyer EDPS-04-1-N Adjustable Differential Pressure Switch
Adjustable differential pressure switch, range .12-1.60" w.c., with M20 connection.
The Series EDPS Adjustable Differential Pressure Switch is designed for pressure, vacuum, and differential pressures. The dual scaled adjustment knob in inches water column and pascals allows changes to the switching pressure to be made without a pressure gage. The EDPS is available with settings from 0.08" w.c. (20 Pa) up to 16" w.c. (4000 Pa). The silicone diaphragm and PA 6.6 body make the series EDPS ideal for use with air and other noncombustible gases. The compact size, adjustment knob and meeting the UL508 standard make the EDPS the perfect choice for H.V.A.C. applications.
Product Applications
- Monitoring air filters and ventilators.
- Monitoring industrial cooling-air circuits.
- Overheating protection for fan heaters.
- Monitoring flows in ventilation ducts.
- Controlling air and fire-protection dampers.
- Frost protection for heat exchanges
Versatile Differential Pressure MonitoringDesigned for use in HVAC, industrial, and air handling applications, the EDPS-04-1-N switch enables precise monitoring of differential air pressure. Its adjustable setpoint and repeatability of 0.1 in w.c. make it well-suited for tasks like filter monitoring, fan control, and static pressure measurement.
Rugged Construction and Flexible MountingCrafted with a durable ABS plastic housing and IP54 protection, this switch resists dust and splashes in demanding environments. It is lightweight at approximately 120 grams and accommodates versatile panel or surface mounting, making installation straightforward with the included mounting screws.
FAQs of Dwyer EDPS-04-1-N Adjustable Differential Pressure Switch:
Q: How do I adjust the setpoint on the Dwyer EDPS-04-1-N pressure switch?
A: The setpoint can be easily adjusted using the integrated knob on the switch front. This allows precise selection within the 0.4 to 4.0 in w.c. (10 to 100 Pa) range, accommodating a wide array of applications in HVAC and air pressure monitoring.
Q: What are the main applications of the EDPS-04-1-N differential pressure switch?
A: This model is ideal for air filter monitoring, fan control, and duct static pressure measurement in HVAC systems. It measures the pressure of air and non-combustible gases, making it suitable for industrial environments.
Q: When should I use a differential pressure switch like this one in my system?
A: You should use this switch whenever monitoring of air flow, filter status, or maintaining proper airflow balance is required in HVAC or similar systems. It helps detect differential pressure changes that indicate filter clogging or fan performance issues.
Q: Where can the Dwyer EDPS-04-1-N be mounted?
A: The switch supports both surface and panel mounting, providing flexibility for installation in control panels, on walls, or directly onto equipment. Mounting screws are provided for ease of setup.
Q: What benefit does the IP54 protection class offer?
A: IP54 protection ensures the device is shielded against dust and splashing water, promoting reliable performance and long-term durability in industrial and HVAC environments.
Q: How accurate and repeatable is the EDPS-04-1-N pressure switch?
A: The switch offers accuracy of 15% of the setpoint and repeatability of 0.1 in w.c., ensuring consistent and dependable pressure monitoring for critical control applications.