About Setra Model 265 Differential Pressure Transducer Range 0- 0.5 Inch
Setra Model 265 Differential Pressure Transducer Range 0- 0.5 Inch
Range- DP TRAN0- 0.5 INCH24 VDC/0-5VDC +/-1% FS W/ CERT
Mack -SETRA USA
Supply Voltage
- Current output-9 to 30VDC @ 20 mA
- Voltage Output- 0-5(10)v output 9(12) to 30VAC @ 0.6 VA; 0-5(10)v output 9(12) to 30V @ 25 mA
- Accuracy- 1% Full scale, Opt .4% and .25%
- Signal Output- 0-5V @ 5K, 4-20mA @ 750 (loop powered)
- Sensor Type- Capacitive
- Adjustments- (Z/S) Zero & Span trim POTs
- Normal Measurement Range- (0 to 100WC) or(0.1 to 50WC)
- Overpressure- (Burst) 10 psid (68.95 kPa)
- Max Operating Pressure- (Proof) -50WC to +100"WC
- Operating Temperature- 0 to 150 (-18 to 65)
- Operating Humidity- 10 to 95% Non-condensing
- Wetted Parts- Stainless steel
- Media Compatibility- Inert dry air
- Process Connection- 3/16OD plastic, for 1/4 OD tubing
- Wiring Exposed terminals- 2-(4-20mA), 3-(Volts)
- Mounting- 2 , #10 screws
- Enclosure Rating- NEMA1 equivalent, plastic UL94-V-0
- Dimensions- 3.16 w x 1.89 h x 1.64d, (8.0 x 4.8 x 4.2 cm)
- Weight- 0.19 lb (0.09 Kg)
- Approvals- CE
- Warranty- 1 year
- 1% accuracy improves variable air volume
- Optional accuracies 0.4% or 0.25% FS
- 24 VDC or 24 VAC excitation
- Signal level 0-5 VDC, 0-10 VDC or 2-Wire 4-20 mA
- UL94-V-), rated for Plenums
- Fully protected against reverse wiring
MORE INFORMATION & RELATED DOCUMENT
- Family Description- TheSetra Model 265 Differential Pressure TransducerProvides Superior Positive and Negative Pressure Sensing Required For High Efficiency, Air-Control Systems. TheModel 265is a 1.0% Full Scale Accuracy unit (0.4%, 0.25% FS Optional) With an Available Snap-on Conduit Enclosure Molded From High Impact Lexan.
- Description -DP TRAN 0- 0.5 INCH 24 VDC/0-5VDC +/-1% FS W/ CERT
- Manufacturer -SETRA USA
High-Precision Differential Pressure SensingEquipped with a capacitive sensor and high-precision processing, the Setra Model 265 provides dependable measurements for differential pressure applications. Its rugged enclosure, anodized aluminum finishing, and sealed silicone components ensure reliable performance and long-term durability in diverse environments.
Flexible Configuration and Simple OperationThe transducers output signal is configurable at the factory to either 0-5 VDC or 4-20 mA, and it operates on multiple power supply options. Zero and span can be fine-tuned using internal potentiometers during commissioning, ensuring accurate calibration for each application. Installation is hassle-free thanks to the screw terminal block and optional mounting bracket.
FAQs of Setra Model 265 Differential Pressure Transducer Range 0- 0.5 Inch:
Q: How is the Setra Model 265 Differential Pressure Transducer typically installed?
A: The Setra Model 265 can be mounted on panels or ducts using its optional mounting bracket kit. Pressure connections are made via 1/8 NPT female ports, and electrical wiring utilizes the provided screw terminal block for secure attachment.
Q: What types of media can this transducer measure?
A: This model is designed to measure differential pressure of air and non-conductive gases. It is not suitable for use with liquids or corrosive gases.
Q: Where can I adjust the zero and span settings on the Model 265?
A: Zero and span adjustments are accessible internally via potentiometers. These allow field calibration to accommodate specific application requirements and ensure precise readings.
Q: What are the benefits of using the Setra Model 265 in industrial settings?
A: Its industrial-grade construction, high accuracy (1% full scale), quick response time (<50 ms), and broad operating temperature range make it highly reliable for HVAC systems, clean room monitoring, and process control, improving efficiency and safety.
Q: When should the pressure transducers output configuration be determined?
A: The output signal (0-5 VDC or 4-20 mA) should be specified when ordering the unit, as it is configured at the factory to suit your system requirements.
Q: Is this device certified for use internationally?
A: Yes, the Setra Model 265 meets CE and RoHS standards, confirming its suitability for global markets and compliance with international safety and environmental directives.
Q: What should I do if the measured pressure exceeds the rated range?
A: The Model 265 is built for overpressure ratings up to 10 psi and a burst pressure of 20 psi. Exceeding these limits may damage the sensor and compromise accuracy. Always use within the specified range to ensure performance and device longevity.