About Sensocon USA 212-D002I-1 Differential Pressure Transmitter
Sensocon USA 212-D002I-1 Differential Pressure Transmitter
The Series 212 Weatherproof Differential Pressure Transmitter can accurately measure positive, negative, or differential pressure and send a corresponding 4-20 mA or 0-10 V output signal. The Series 212 Weatherproof Differential Pressure Transmitter is designed with an IP 65 enclosure and can be easily mounted to any flat surface. The Series 212 is not position sensitive and can be mounted in any orientation without compromising accuracy. The compact, lightweight design makes installation simple and easy.
SPECIFICATIONS
- Maximum Pressure: Ranges 5 PSI (35 kPa) = 15 PSI (100kPa) MaxRanges > 5 PSI (35 kPa) = 30 PSI (200kPa) Max
- Media compatibility: Air and compatible non-combustible, non-corrosive gases
- Accuracy: Ranges 4" w.c. (1kPa) 1.0%Ranges 5" w.c. (1.25kPa) 0.25%
- Temperature Ranges: Compensated: 15 to 120F (-10 to 50C)Operating: -10 to 155F (-25 to 70C)
- Thermal Effect: +/- 0.028% FS/F (+/- 0.50% FS/C)
- Stability: +/- 0.25% FS/year
- Output Signal: 4-20 mA, 2-wire or 0 - 10 V
- Loop Resistance: 250 @ 24 VDC
- Power Supply: 12-30 VDC
- Enclosure Rating: IP 65
- Electrical Connections: screw terminals
- Electrical Entry: PG7 Cable Gland
- Process Connection: Barbed fittings for 3/16 flexible tubing
- Agency Approvals:CE
Optimized for Industrial Air ApplicationsWith an operating temperature range of -10C to +60C, the Sensocon USA 212-D002I-1 transmitter is built for environments like HVAC installations, clean rooms, and filter monitoring. Its IP54 front ingress rating safeguards the device against dust and splashes, making it suitable for typical industrial and commercial settings where air and non-corrosive gas measurement is essential.
User-Friendly Digital Display and AdjustmentsThe integrated digital LED display provides clear and immediate readings of differential pressure values. Zero and span can be quickly calibrated with push buttons, streamlining setup and minimizing downtime. The intuitive design ensures that users can make precise adjustments without requiring complex instrumentation knowledge.
Reliable Measurements with Fast ResponseEngineered with a fast response time of 100 ms and accuracy of 1% full scale, this device offers dependable real-time monitoring. The 4-20 mA signal output in a 2-wire industrial format ensures compatibility with most building management and automation systems, enabling seamless data integration for efficient process control.
FAQs of Sensocon USA 212-D002I-1 Differential Pressure Transmitter:
Q: How do I install the Sensocon 212-D002I-1 differential pressure transmitter?
A: This model supports both panel and surface mounting. Begin by securing the unit using the included mounting screws. Connect the high and low pressure ports (1/8" NPT female threads) to the appropriate pressure lines. Complete the wiring with the screw terminal connections for your 12-30 VDC power source and signaling, then refer to the instruction manual for detailed setup.
Q: What are the primary applications for this pressure transmitter?
A: This device is ideal for monitoring differential pressure in HVAC systems, clean rooms, filter monitoring, and in-duct air velocity measurements. It reliably measures pressures of air and other non-corrosive gases in both commercial and industrial settings.
Q: When should I perform zero and span calibration, and how is it done?
A: Zero and span calibration should be performed during initial installation and any time you notice a drift in readings. Use the push button controls on the front panel for quick calibration, following the step-by-step process outlined in the instruction manual.
Q: Where is the digital display located, and what information does it show?
A: The digital LED display is located on the front face of the transmitter. It provides real-time differential pressure readings, ensuring users can quickly monitor system conditions at a glance.
Q: What kind of environments can this transmitter operate in?
A: With its IP54-rated front and an operating temperature range from -10C to +60C, the transmitter is designed for use in demanding industrial, commercial, and controlled environments where reliable air or gas pressure monitoring is required.
Q: How does the fast response time benefit my application?
A: A 100 ms response time ensures immediate reaction to pressure changes, which is vital in dynamic systems for process control, safety, and maintaining environmental standards in critical applications such as clean rooms and air handling units.